PRODUCT DESCRIPTION
ISO-FLAME PLUG S 90, is a specially developed form for a quick, easy and clean fitting for fire protection of single cables, cable bundles on circular openings (e.g. core hole) in fire walls and ceilings in accordance to DIN 4102. It consists of fire resistant impregnated PU high resilient foam and its maximum fire resistance durability averages between, at least, 60 and 90 minutes.
PRODUCT ADVANTAGES
- Quick and clean application without special tools (very economical)
- Totally free from dust and fibres
- Easy fitting of cables
- No special tools for fitting required or preparation of wall and ceiling openings necessary
- Toxic fume blocker
- Flexible application (temporary and permanent fire protection)
- No cracking due to permanent elasticity with high flexibility
- Free from halogens and solvents
- 10 year performance guarantee*
*On the conditions of the manufacturer (available upon request).
Applications
ISO-FLAME PLUG S 90 is suitable for fire-stop protection in wall and ceiling openings where fire protection rating S 30, S 60 or S 90 is requiered, in accordance with DIN 4102 T.9. It is particularly suitable for fire protection walls and ceilings of concrete and/or reinforced concrete, cellular concrete, brick-work or lighter partitioning walls. The fitting of cables is simply done by cutting.
Technical approval
Building authorities approval through DIBt Berlin for S 90 (Z-19.15-1575).
Technical data | Standard | Classification |
Material description | fire resistant impregnated PUR-flexible foam | |
Colour | anthracite | |
Fire resistance durability in fire protection walls and ceilings | DIN 4102 T.9 | S 90 |
Building material approval (ABZ) | S 90-le Z-19.15-1575 | |
Handling temperature | +5°C to +40°C | |
Temperature stability range, dry | -40°C to +80°C | |
Building material class | DIN 4102 T.1 | B2 |
Dimension tolerance | DIN 7715 T5 P3 | requirements fulfilled |
Shelf life | 1 year |
Preparation
- Coat either the wall aperture edges, or the ISO-FLAME PLUG edges with ISO-FLAME KITT to bond the foam in place.
- On ceiling openings both visible fire-stop surfaces are to be coated with ISO-FLAME KITT. This is optional on walls
- The relevant building approval should be sort for using the ISO-FLAME PLUG S 90 as the services fire stop.
System accessories
- ISO-FLAME KITT: ablative fire protection compound (paste consistency, white) ABZ Z-19.11-1571. ISO-FLAME SET: construction approval incl. conformity specifications, completion sign.
D x T (mm) = article nr. |
Max. hole diameter |
Achieved F-Class** |
Minimum wall and ceiling thickness |
Carton (Plugs) |
54 x 90 | 51 mm | up to S 90 | 30 | |
62 x 90 | 58 mm | up to S 90 | 30 | |
74 x 90 | 70 mm | up to S 90 | 100 mm (wall) | 18 |
85 x 90 | 80 mm | up to S 90 | 12 | |
100 x 90 | 95 mm | up to S 90 | ja | 12 |
115 x 90 | 109 mm | up to S 90 | 12 | |
130 x 90 | 123 mm | up to S 90 | 150 mm (ceiling) | 12 |
151 x 90 | 143 mm | up to S 90 | 12 | |
181 x 90 | 175 mm | up to S 90 | 12 |
** For fire protection class S 90 the minimum thickness of the fire-stop is 200 mm. 2 bricks per opening must be installed. |
Details and information presented in this document are based on the best knowledge available at the time. They are intended for general information purposes, and it is recommended that users conduct their own tests under their specific conditions to ensure the product’s suitability for its intended use. No definitive guarantee or liability can be given regarding the details or the absolute completeness of the information provided in these guidelines. We reserve the right to improve or modify technical specifications and information without prior notice.